TECHNICAL SPECIFICATIONS
Main Run time for load 2700W
Min-max: 270-2700 W 3min 58s
Max. Capacity Used 100 %
Main Input Voltage 230 V
Other Input Voltage 220 V 240 V
Main Output Voltage 230 V Other Output Voltage 220 V 240 V
rated power in W 2700 W
Rated power in VA 3000 VA
Input Connection Type BS1363A British IEC 60320 C20 Schuko CEE 7 / EU1-16P
output connection type 8 IEC 60320 C13 2 IEC Jumpers 2 IEC 60320 C19
Number of rack unit 2U
Cable length 2.44 m
Number of cables 1
Battery type Lead-acid battery
Provided equipment CD with software Documentation CD Installation guide Rack mounting brackets Rack mounting support rails USB cable Warranty card
Batteries & Runtime Run Time Efficiency
Number of battery filled slots 1
Battery recharge time 3 h
Number of battery replacement quantity 1
Additional information Configurable for 220 : 230 or 240 nominal output voltage
Battery voltage 96 V
Battery charger power 168 W rated
Battery power in VAH 505 VAh runtime
Battery life 3…5 year(s)
Replacement battery APCRBC152
Battery option SRT96RMBP 1 1515 VAh SRT96RMBP 2 2525 VAh SRT96RMBP 3 3535 VAh SRT96RMBP 4 4545 VAh SRT96RMBP 5 5555 VAh SRT96RMBP 6 6565 VAh SRT96RMBP 8 8585 VAh SRT96RMBP 10 10605 VAh
Extended runtime 1
General product web sub-family High density
Number of power module free slots 0
Number of power module filled slots 0
Redundant No
Physical Colour Black
Height 8.5 cm
Width 43.2 cm
Depth 63.5 cm
Product weight 31.3 kg
Mounting location Front
Mounting preference Lower
Mounting mode Rack-mounted
Two post mountable 0
USB compatible Yes
Mounting position Horizontal
Input Network frequency 40...70 Hz auto-sensing
Input voltage limits 100...275 V adjustable (half load)
Output Maximum configurable power in W 2700 W
Harmonic distortion Less than 2 %
Output frequency 50/60 Hz +/- 3 Hz sync to mains
Crest factor 3 : 1
UPS type Double conversion online
Wave type Sine wave
bypass type Internal bypass (automatic and manual)
Maximum configurable power in VA 3000 VA
Conformance Product certifications CE EAC RCM VDE Marking CE Mark
Standards EN/IEC 62040-1:2019/A11:2021 EN/IEC 62040-2:2006/AC:2006 EN/IEC 62040-2:2018
Environmental Ambient air temperature for operation 0…40 °C
Relative humidity 0…95 % non-condensing
Operating altitude 0...10000 ft
Ambient air temperature for storage -15…45 °C
Storage Relative Humidity 0…95 % non-condensing
Storage altitude 0.00…15240.00 m
Acoustic level 55 dBA
Heat dissipation 703 Btu/h
IP degree of protection IP20
Communications & Management Free slots 1
Alarm Audible and visible alarms : prioritized by severity Emergency power off Yes
Surge Protection and Filtering Surge energy rate 340 J
Packing Units Unit Type of Package 1 PCE Number o f Units in Package 1 1
Package 1 Height 24.6 cm
Package 1 Width 59.9 cm
Package 1 Length 87.1 cm
Package 1 Weight 39.92 kg |