TECHNICAL SPECIFICATIONS
Main Run time for load 4500W
Min-max: 450-4500 W 3min 59s
Max. Capacity Used 100 %
Main Input Voltage 230 V
Other Input Voltage 220 V 240 V
Main Output Voltage 230 V Other Output Voltage 220 V 240 V
rated power in W 4500 W
Rated power in VA 5000 VA
output connection type 6 IEC 60320 C13
2 IEC Jumpers 4 IEC 60320 C19
Number of rack unit 3U
Battery type Lead-acid battery
Provided equipment Documentation CD Installation guide Rack mounting hardware Rack mounting brackets Rack mounting support rails Temperature probe
Warranty card Web/SNMP management card
Batteries & Runtime Run Time Efficiency
Number of battery filled slots 0
Battery recharge time 1.5 h
Number of battery replacement quantity 1
Battery voltage 192 V
Battery charger power 560 W rated
Battery power in VAH 845 VAh runtime Battery life
3…5 year(s)
Replacement battery APCRBC140
Battery option SRT192RMBP 1 2535 VAh SRT192RMBP 2 4225 VAh SRT192RMBP 3 5915 VAh SRT192RMBP 4 7605 VAh SRT192RMBP 5 9295 VAh SRT192RMBP 6 10985 VAh SRT192RMBP 8 14365 VAh SRT192RMBP 10 17745 VAh
Extended runtime 1
General product web sub-family High density
Number of power module free slots 0
Number of power module filled slots 0
Redundant No
Physical Colour Black
Height 13 cm
Width 43.2 cm
Depth 71.94 cm
Product weight 54.43 kg
Mounting location Front
Mounting preference No preference
Mounting mode Rack-mounted
Two post mountable 0
USB compatible Yes
Mounting position Horizontal
Input Network frequency 40...70 Hz auto-sensing
Number of input connectors 1 hard wire 3-wire (1P + N + E) Input voltage limits
100...275 V adjustable (half load)
Output Maximum configurable power in W 4500 W
Harmonic distortion Less than 2 %
Output frequency 50/60 Hz +/- 3 Hz sync to mains
Crest factor 3 : 1
UPS type Double conversion online
Wave type Sine wave
bypass type Internal bypass (automatic and manual)
Maximum configurable power in VA 5000 VA
Conformance Product certifications CE EAC IRAM RCM VDE Marking CE Mark
Standards EN/IEC 62040-1:2019/A11:2021 EN/IEC 62040-2:2006/AC:2006 EN/IEC 62040-2:2018
Environmental Ambient air temperature for operation 0…40 °C
Relative humidity 0…95 % non-condensing
Operating altitude 0...10000 ft
Ambient air temperature for storage -15…45 °C
Storage Relative Humidity 0…95 % non-condensing
Storage altitude 0.00…15240.00 m
Acoustic level 55 dBA
Heat dissipation 931 Btu/h
IP degree of protection IP20
Communications & Management Free slots 1
Preinstalled device Network management card 3 with environmental monitoring
Alarm Audible and visible alarms : prioritized by severity Emergency power off Yes
Surge Protection and Filtering Surge energy rate 480 J
Packing Units Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 33 cm
Package 1 Width 61 cm
Package 1 Length 96 cm
Package 1 Weight 66.86 kg |