TECHNICAL SPECIFICATIONS
Main Run time for load 1980W
Min-max: 198-1980 W 9min 45s
Max. Capacity Used 100 %
Main Input Voltage 208 V 230 V
Other Input Voltage 220 V 240 V
Main Output Voltage 208 V 230 V
Other Output Voltage 208 V 220 V 240 V
rated power in W 1980 W
Rated power in VA 2200 VA
Input Connection Type IEC 320 C20
Schuko CEE 7 / EU1-16P BS1363A British
output connection type 8 IEC 320 C13 2 IEC Jumpers 2 IEC 320 C19
Number of rack unit 4U
Cable length 2.00 m
Number of cables 1
Battery type Lead-acid battery
Provided equipment CD with software Documentation CD Rack mounting support rails Smart UPS signalling RS-232 cable User manual USB cable
Batteries & Runtime Run Time Efficiency
Extended runtime 1
Number of battery filled slots 0
Number of battery free slots 0
Battery recharge time 3 h
Number of battery replacement quantity 1
Battery life 3…5 year(s)
Replacement battery APCRBC143
Battery power in VAH 702 VAh runtime
Battery charger power 233 W rated
Battery option SMX120BP 1 2106 VAh SMX120BP 2 3510 VAh SMX120BP 3 4914 VAh SMX120BP 4 6318 VAh SMX120BP 6 9126 VAh SMX120BP 8 11934 VAh SMX120BP 10 14742 VAh
General Number of power module 1750
Number of power module filled slots 0
Number of power module free slots 0
product web sub-family Extended run Redundant No
Physical Colour Black
Height 43.2 cm
Width 17.8 cm
Depth 48.3 cm
Product weight 38.56 kg
Mounting location Front
Mounting preference Lower
Mounting mode Rack-mounted
Two post mountable 1
USB compatible Yes
Input Input voltage limits 140...280 V
Network frequency 50/60 Hz +/- 3 Hz auto-sensing
Output Harmonic distortion Less than 5 %
Maximum configurable power in VA 2200 VA Maximum configurable power in W 1980 W
Transfer time 6 ms typical : 10 ms maximum
UPS type Line interactive Wave type Sine wave
Output frequency 50/60 Hz +/- 3 Hz sync to mains
Conformance Product certifications CE CSA EAC IRAM RCM VDE
Standards EN/IEC 62040-1:2019/A11:2021 EN/IEC 62040-2:2006/AC:2006 EN/IEC 62040-2:2018
Environmental Acoustic level 55 dBA
Heat dissipation 150 Btu/h
Operating altitude 0...10000 ft
Ambient air temperature for operation 0…40 °C
Ambient air temperature for storage -15…45 °C
Storage altitude 0.00…15240.00 m
Relative humidity 0…95 %
Storage Relative Humidity 0…95 %
Communications & Management Control panel Multifunction LCD status and control console
Emergency power off Yes
Free slots 1
Control panel LED status display with on line : on battery : replace battery and overload indicators
Alarm Alarm when on battery : distinctive low battery alarm : configurable delays Surge Protection and Filtering Surge energy rate 645 J
Noise suppression Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449 Packing Units Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 33 cm
Package 1 Width 63.3 cm
Package 1 Length 58.6 cm
Package 1 Weight 47.73 kg
Pallet unit layers 2
Pallet layers 4 |