SPECIFICATIONS
Brand POWERSHIELD
Model Number PSAS400T
Internal circuit of DB-9 port RS-232 port 9-pin port
Electric Parameter of DB-9 port Parameter Resistor DC Current Symbol: IR Max : 6 Min : 1 Unit: mA
Diode Reverse Voltage Symbol: VR Max: 6 Min: - Unit: V
Forward Current Symbol: IF Max: 50 Min: - Unit: mA
Peak Forward Current Symbol: IF (Peak) Max: 1 Min: - Unit: A
Relay DC Voltage Symbol: VDC Max: 24 Min: - Unit: V
DC Current Symbol: IDC Max: 1 Min: - Unit: A
Weight 0.15 kg
Dimensions 160 × 125 × 50 mm
Pin Assignment Pin Assignment Function I/O Pin 1 UPS Failure O/P Pin 2 UPS Audible Alarm O/P Pin 3 GND (Common for Pin 4) Power Ground Pin 4 Remote Shutdown I/P Pin 5 Common for Relays Power Supply Pin 6 Bypass Active O/P Pin 7 Low Battery O/P Pin 8 UPS On O/P Pin 9 Utility Failure O/P P.S. The shutdown pin (pin4 & pin3) only accepts 3-10s high level signal to perform the UPS shutdown.
Function Description AC Status:Pin 1 & Pin 5 connected AO Status:Pin 1 & Pin 5 disconnected Reason: UPS failure
AC Status:Pin 2 & Pin 5 connected AO Status: Pin 2 & Pin 5 disconnected Reason: UPS failure, utility failure, low battery, bypass active
AC Status: Pin 6 & Pin 5 connected AO Status: Pin 6 & Pin 5 disconnected Reason: Bypass active
AC Status: Pin 7 & Pin 5 connected AO Status: Pin 7 & Pin 5 disconnected Reason: Battery voltage is low
AC Status: Pin 8 & Pin 5 connected AO Status: Pin 8 & Pin 5 disconnected Reason: UPS is in inverter mode AC Status: Pin 9 & Pin 5 connected AO Status: Pin 9 & Pin 5 disconnected Reason: Utility failure |